Installation Instructions

Documents pareils
Paxton. ins Net2 desktop reader USB

Notice Technique / Technical Manual

Fabricant. 2 terminals

PVCHECK Rel /11/12

Contrôle d'accès Access control. Notice technique / Technical Manual

03/2013. Mod: WOKI-60IP/TR. Production code: DTWIC 6000

GIGABIT PCI DESKTOP ADAPTER DGE-530T. Quick Installation Guide+ Guide d installation+

NORME INTERNATIONALE INTERNATIONAL STANDARD. Dispositifs à semiconducteurs Dispositifs discrets. Semiconductor devices Discrete devices

Package Contents. System Requirements. Before You Begin

Quick Start Guide This guide is intended to get you started with Rational ClearCase or Rational ClearCase MultiSite.

Le No.1 de l économie d énergie pour patinoires.

Software and Hardware Datasheet / Fiche technique du logiciel et du matériel

Railway Operating Certificate Regulations. Règlement sur les certificats d exploitation de chemin de fer CODIFICATION CONSOLIDATION

Garage Door Monitor Model 829LM

Règlement sur le télémarketing et les centres d'appel. Call Centres Telemarketing Sales Regulation

Frequently Asked Questions

Logitech Tablet Keyboard for Windows 8, Windows RT and Android 3.0+ Setup Guide Guide d installation

Contents Windows

This is a preview - click here to buy the full publication NORME INTERNATIONALE INTERNATIONAL STAN DARD. Telecontrol equipment and systems

RULE 5 - SERVICE OF DOCUMENTS RÈGLE 5 SIGNIFICATION DE DOCUMENTS. Rule 5 / Règle 5

Guide d'installation rapide TFM-560X YO.13

Folio Case User s Guide

DOCUMENTATION - FRANCAIS... 2

The new consumables catalogue from Medisoft is now updated. Please discover this full overview of all our consumables available to you.

Warning: Failure to follow these warnings could result in property damage, or personal injury.

Cheque Holding Policy Disclosure (Banks) Regulations. Règlement sur la communication de la politique de retenue de chèques (banques) CONSOLIDATION

SYSTÈME DE GAINES À SPIRALE ET RACCORDS TOURNANTS

SunATM 4.0 Release Notes

Instructions Mozilla Thunderbird Page 1

SERVEUR DÉDIÉ DOCUMENTATION

SA-32 / SA-62 INSTRUCTION MANUAL - MANUEL D INSTRUCTIONS

Spécial Catégorie 6 Patch Cords

Master4Light. Caractérisation Optique et Electrique des Sources Lumineuses. Equipement 2-en-1 : source de courant et spectrophotomètre

R.V. Table Mounting Instructions

How to Login to Career Page

DOCUMENTATION - FRANCAIS... 2

Thank you for choosing the Mobile Broadband USB Stick. With your USB Stick, you can access a wireless network at high speed.

General Import Permit No. 13 Beef and Veal for Personal Use. Licence générale d importation n O 13 bœuf et veau pour usage personnel CONSOLIDATION

ASSEMBLY INSTRUCTIONS DIRECTIVES POUR L'ASSEMBLAGE ombre pendant lamp lampe suspendue à tons dégradés, chocolat

ASSEMBLY INSTRUCTIONS DIRECTIVES POUR L'ASSEMBLAGE luster chandelier lamp chandelier à trois branches en verre lustré

accidents and repairs:

Practice Direction. Class Proceedings

User guide Conference phone Konftel 100

INVESTMENT REGULATIONS R In force October 1, RÈGLEMENT SUR LES INVESTISSEMENTS R En vigueur le 1 er octobre 2001

Panorama des bonnes pratiques de reporting «corruption»

AMENDMENT TO BILL 32 AMENDEMENT AU PROJET DE LOI 32

ARP-090G / ARP-090K NOTICE D'EMPLOI INSTRUCTION MANUAL

Ships Elevator Regulations. Règlement sur les ascenseurs de navires CODIFICATION CONSOLIDATION. C.R.C., c C.R.C., ch. 1482

Monitor LRD. Table des matières

Compléter le formulaire «Demande de participation» et l envoyer aux bureaux de SGC* à l adresse suivante :

APPENDIX 6 BONUS RING FORMAT

Exercices sur SQL server 2000

LOI SUR LA RECONNAISSANCE DE L'ADOPTION SELON LES COUTUMES AUTOCHTONES ABORIGINAL CUSTOM ADOPTION RECOGNITION ACT

Instructions pour mettre à jour un HFFv2 v1.x.yy v2.0.00

Stérilisation / Sterilization

BILL 203 PROJET DE LOI 203

Archived Content. Contenu archivé

English Q&A #1 Braille Services Requirement PPTC Q1. Would you like our proposal to be shipped or do you prefer an electronic submission?

Grandes tendances et leurs impacts sur l acquisition de produits et services TI.

MODULES ÉLECTRIQUES. - systèmes électriques DC - onduleurs - convertisseurs - interrupteurs statiques. Notre alimentation Votre confiance

Critères à l attention des fabricants et des fournisseurs de biens ou de services : dispositifs mécaniques pour bingo

Once the installation is complete, you can delete the temporary Zip files..

F1 Security Requirement Check List (SRCL)

Moteur DC: Comment faire varier sa vitesse?

INTERNATIONAL STANDARD NORME INTERNATIONALE


Principe de TrueCrypt. Créer un volume pour TrueCrypt

Utiliser une WebCam. Micro-ordinateurs, informations, idées, trucs et astuces

PARIS ROISSY CHARLES DE GAULLE

CLIM/GTP/27/8 ANNEX III/ANNEXE III. Category 1 New indications/ 1 re catégorie Nouvelles indications

INTERNATIONAL STANDARD NORME INTERNATIONALE

Laboratory accredited by the French Home Office (official gazette date February 5 th, 1959, modified) Valid five years from August 27 th, 2013

Conférence Bales II - Mauritanie. Patrick Le Nôtre. Directeur de la Stratégie - Secteur Finance Solutions risques et Réglementations

GASKET FOR TONER COLLECTION BOTTLE

Règlement relatif à l examen fait conformément à la Déclaration canadienne des droits. Canadian Bill of Rights Examination Regulations CODIFICATION

INDIVIDUALS AND LEGAL ENTITIES: If the dividends have not been paid yet, you may be eligible for the simplified procedure.

Discours du Ministre Tassarajen Pillay Chedumbrum. Ministre des Technologies de l'information et de la Communication (TIC) Worshop on Dot.

POLICY: FREE MILK PROGRAM CODE: CS-4

If the corporation is or intends to become a registered charity as defined in the Income Tax Act, a copy of these documents must be sent to:

NEW Fin Fan / Air cooled condenser cleaning

Name Use (Affiliates of Banks or Bank Holding Companies) Regulations

Product Overview Présentation produits

IPSAS 32 «Service concession arrangements» (SCA) Marie-Pierre Cordier Baudouin Griton, IPSAS Board

APPENDIX 2. Provisions to be included in the contract between the Provider and the. Holder

Quick Installation Guide TEW-AO12O

that the child(ren) was/were in need of protection under Part III of the Child and Family Services Act, and the court made an order on

Embases pour raccordement G1/8 - G1/4

Convergy : la conversion d énergie par excellence

TABLE DES MATIERES A OBJET PROCEDURE DE CONNEXION

Lavatory Faucet. Instruction Manual. Questions?

This is a preview - click here to buy the full publication NORME CEI INTERNATIONALE IEC INTERNATIONAL STAN DARD

en SCÈNE RATIONAL Rational Démonstration SDP : automatisation de la chaîne de développement Samira BATAOUCHE sbataouche@fr.ibm.com

Thank you for choosing the Mobile Broadband USB Stick. With your USB Stick, you can access a wireless network at high speed.

Support Orders and Support Provisions (Banks and Authorized Foreign Banks) Regulations

HUAWEI TECHNOLOGIES CO., LTD. channelroad. A better way. Together.

INTERNATIONAL CONSULTANT & SUPPLIERS TO THE WINE & SPIRITS TRADE

Institut français des sciences et technologies des transports, de l aménagement

Information Equipment

PRESENTATION REMOTE TÉLÉCOMMANDE DE PRÉSENTATION. User Guide Manuel de l utilisateur

Natixis Asset Management Response to the European Commission Green Paper on shadow banking

Transcription:

Installation Instructions (Cat. No. 1794-PS3) 1 2 3 4 5 7 6 Component Identification 1 Power Supply module 1794-PS3 2 Indicator 3 120/230V ac ground 4 120/230V ac common L2/N connections 5 120/230V ac power L1 connections 6 +24V dc connections 7 24V common connections! ATTENTION: The 1794-PS3 power supply provides sufficient 24V dc power to operate 6 adapter modules. You can use this power supply to operate an entire FLEX I/O system as long as you do not exceed a total of 3A. FLEX I/O is a trademark of Rockwell Automation.

2 FLEX I/O Power Supply European Union Directive Compliance If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives. EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: EN 50081-2EMC Generic Emission Standard, Part 2 Industrial Environment EN 50082-2EMC Generic Immunity Standard, Part 2 Industrial Environment This product is intended for use in an industrial environment. Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131 2 Programmable Controllers, Part 2 Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications: Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1 Guidelines for Handling Lithium Batteries, publication AG-5.4 Open style devices must be provided with environmental and safety protection by proper mounting in enclosures designed for specific application conditions. See NEMA Standards publication 250 and IEC publication 529, as applicable, for explanations of the degrees of protection provided by different types of enclosures.

FLEX I/O Power Supply 3 Installing the Power Supply A B C C 1. Position the power supply module A on a 35 x 7.5mm DIN rail B (A-B pt. no. 199-DR1) at 30 o angle. 2. Rotate the power supply module onto the DIN rail with the top of the rail hooked under the lip on the rear of the adapter module. 3. Press the power supply module down onto the DIN rail until flush. Locking tab (C) will snap into position and lock the adapter module to the DIN rail. 4. If the power supply module does not lock in place, use a screwdriver or similar device to move the locking tab down while pressing the adapter module flush onto the DIN rail and release the locking tab to lock the adapter module in place. If necessary, push up on the locking tab to lock. 5. Connect the power supply wiring as shown under Wiring.. NOTE: For Panel/Wall mounting, refer to publication 1794-5.13, Panel Mounting Kit, Cat. No. 1794-NM1.

4 FLEX I/O Power Supply Wiring Power 24V DC POWER SUPPLY 1794-PS3 A B C F ED COM 24V H I J G ATTENTION: The 1794-PS3 power supply provides sufficient 24V dc power to operate 6 adapter modules. You can use this power supply to operate an entire FLEX I/O system as long as you do not exceed a total of 3A. Terminals A, B and C are 120/230V supply terminals. Terminals D, E and F are available to daisychain this 120/230V power to other 1794-PS3 power supplies. If supplying 120V ac to the power supply, you can also power the ac modules in the adjacent system. Torque screw terminals to 5 7 lb-in when making connections. 1. Connect the 120/230V ac power to the left side terminals on the connectors on the left side of the module as follows: Connect To ac Ground GND A 120/230V ac common L2/N B 120/230V ac power L1 C 2. Connect terminal G (+24V dc) to the +24V dc terminal on the first adapter. 3. Connect terminal H (+24V dc common) to the +24V dc common terminal on the first adapter. 4. Repeat steps 3 and 4 using terminals I and J for the second adapter. 5. Connections D, E and F are used to pass 120/230V ac power to adjacent 1794-PS3 power supplies.

FLEX I/O Power Supply 5 Important: Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in accordance with the authority having jurisdiction. Example of Using a 1794-PS3 Power Supply to Power 4 Adapter Modules Power Supply Adapter 24V dc All dc powered I/O modules 24V dc from separate source Adapter 24V dc ac All ac powered I/O modules Adapter 24V dc ac All ac powered I/O modules 24V dc Adapter 120V ac 24V dc from separate source Combination ac and dc powered I/O modules

6 FLEX I/O Power Supply Diagnostic Indicator Power Indicator Power 24V DC POWER SUPPLY 1794-PS3 COM 24V The power indicator is on (green) when voltage at the output is between 20.4V dc and 28V dc. Indicator ON (green) OFF Description Output voltage is greater than 20.4V dc, but less than 28V dc No power applied to power supply. Output voltage exceeded 35V dc, and overvoltage protection shut down unit. Output current is above 3A.

FLEX I/O Power Supply 7 Safety Approvals UL certifies products for general use as well as for use in hazardous locations. UL certification can be done to United States (US) safety standards and/or Canadian (C) safety standards. Actual CUL certification is indicated by the product label as shown below, and not by statements in any user documentation. Example of the CUL certification product label for a product evaluated to both US and C safety standards I Approbation de sécurité La UL certifie les produits d utilisation générale aussi bien que ceux qui s utilisent dans des emplacements dangereux. Les certifications UL peuvent être rédigées selon les normes de sécurité des Etats Unis (US) et/ou les normes de sécurité du Canada (C). La certification CUL en vigueur est indiquée par l étiquette du produit et non par des affirmations dans la documentation à l usage des utilisateurs. Exemple d étiquette de certification UL d un produit évalué selon les normes de sécurité des Etats Unis et du Canada. I To comply with UL certification for use in hazardous locations, the following information becomes a part of the product literature for UL-certified Allen-Bradley industrial control products. This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only. The products having the appropriate UL markings (that is, Class I, Division 2, Groups A, B, C, D), are certified for use in other equipment where the suitability of combination (that is, application or use) is determined by the UL, CSA or the local inspection office having jurisdiction. Peripheral equipment must be suitable for the location in which it is used. Important: Due to the modular nature of a PLC control system, the product with the highest temperature rating determines the overall temperature code rating of a PLC control system in a Class I, Division 2 location. The temperature code rating is marked on the product label as shown. Temperature code rating I Pour satisfaire à la certification de la UL dans des endroits dangereux, les informations suivantes font partie intégrante de la documentation des produits industriels de contrôle Allen-Bradley certifiés par la UL. Cet équipement convient à l utilisation dans des emplacements de Classe I, Division 2, Groupes A, B, C, D, ou ne convient qu à l utilisation dans des endroits non dangereux. Les produits portant le marquage approprié de la UL (c est à dire, Classe I, Division 2, Groupes A, B, C, D) sont certifiés à l utilisation pour d autres équipements où la convenance de combinaison (application ou utilisation) est déterminée par la UL, CSA ou le bureau local d inspection qualifié. L équipement périphérique doit convenir à l emplacement d utilisation. Important: Par suite de la nature modulaire du système de contrôle PLC, le produit ayant le taux le plus élevé de température détermine le taux d ensemble du code de température du système de contrôle d un PLC dans un emplacement de Classe I, Division 2. Le taux du code de température est indiqué sur l étiquette du produit. Taux du code de température I Look for temperature code rating here The following warnings apply to products having CUL certification for use in hazardous locations. Le taux du code de température est indiqué ici Les avertissements suivants s appliquent aux produits ayant la certification CUL pour leur utilisation dans des emplacements dangereux.

8 FLEX I/O Power Supply Safety Approvals WARNING: Explosion hazard Substitution of components may impair suitability for Class I, Division 2. Do not replace components unless power has been switched off or the area is known to be non-hazardous. Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous. Do not disconnect connectors unless power has been switched off or the area is known to be non-hazardous. Secure any user-supplied connectors that mate to external circuits on an Allen-Bradley product using screws, sliding latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for a minimum of one minute. Approbation de sécurité AVERTISSEMENT: Risque d explosion La substitution de composants peut rendre ce matériel inacceptable pour lesemplacements de Classe I, Division 2. Couper le courant ou s assurer quel emplacement est désigné non dangereux avant de remplacer lescomposants. Avant de déconnecter l équipement, couper le courant ou s assurer que l emplacement est désigné non dangereux. Avant de débrancher les connecteurs, couper le courant ou s assurer que l emplacement est reconnu non dangereux. Attacher tous connecteurs fournis par l utilisateur et reliés aux circuits externes d un appareil Allen-Bradley à l aide de vis, loquets coulissants, connecteurs filetés ou autres moyens permettant aux connexions de résister à une force de séparation de 15 newtons (3,4 lb. - 1,5 kg) appliquée pendant au moins une minute. Le sigle CUL est la marque déposée de Underwriters Laboratories. PLC est une marque déposée de Allen-Bradley Company, Inc. CUL logo is a registered trademark of the Underwriters Laboratories PLC is a registered trademark of Allen-Bradley Company, Inc.

FLEX I/O Power Supply 9 Specifications Power Supply Cat. No. 1794-PS3 Note: This power supply complies with the CE Low Voltage Directive. Input Specifications Nominal Supply Voltage Voltage Range Input Current Inrush Current Interruption Output Specifications Nominal Output Voltage Voltage Range Output Current Output Power Output Ripple Minimum Load Output Surge Overvoltage Protection Overcurrent Protection Leakage Current Isolation Voltage 120V ac, 47 63Hz; 1.7A maximum 230V ac, 47 63Hz; 1.1A maximum 85-265V ac 1.9A maximum 40A typical, 1 ac cycle @ V in 265V ac, 55 o C Output voltage will stay within specification when input drops out for 1/2 cycle @ 47Hz, 85V ac with maximum load +24V dc 20.4 27.6V dc (includes noise and 5% ac ripple) 3A maximum (horizontal mount; 2.8A maximum all other mounting (See Derating Curve) 72W 1200mV peak-to-peak maximum 50mA Sufficient to drive 6 adapters Output internally limited to 35V dc. Cycle power to reenergize. Current limit 3.2A minimum (107% minimum) 0.5mA rms maximum @ rated input and output 2500V dc for 1 second Specifications continued on next page.

10 FLEX I/O Power Supply Specifications Power Supply Cat. No. 1794-PS3 General Specifications Mounting Terminal Screw Torque Dimensions Inches Millimeters Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Shock Conductors Operating Non-operating Vibration Wire Size Category Horizontal or vertical on a DIN rail, wall or panel 5 7 lb-in (0.5 0.6Nm) 3.4H x 3.7W x 2.7D 87H x 94W x 69D 0 to 55 o C (32 to 131 o F) (See Derating Curve) 40 to 85 o C ( 40 to 185 o F) 5 to 95% noncondensing 30 g peak acceleration, 11(+1)ms pulse width 50 g peak acceleration, 11(+1)ms pulse width Tested 5 g @ 10 500Hz per IEC 68-2-6 12 gauge (4mm 2 ) stranded maximum 3/64 inch (1.2mm) insulation maximum 1 1 1 You use this category information for planning conductor routing as described in publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

FLEX I/O Power Supply 11 Derating Curve 3.0 2.8 ÉÉ 2.5 Max. Output Current (A) 2.0 1.5 1.0 0.5 0 0 10 20 30 40 50 55 60 Ambient Temperature o C The area within the curve represents the safe operating range for the module under various conditions of user supplied 24V dc supply voltages and ambient temperatures. = Normal mounting safe operating range, (includes ). = Other mounting positions (including inverted horizontal) safe operating range Normal Mounting Horizontal Other Mounting (including Vertical, and Inverted Horizontal Mounting)

12 FLEX I/O Power Supply Mounting Dimensions Inches (Millimeters) 3.4 (87) 3.2 (80) 3.7 (94) 1794-PS3 3.4H x 3.7W x 2.7D (87H x 95W x 69D) A = DIN rail B = Secure DIN rail approximately every 200mm Power COM 24V DC POWER SUPPLY 1794-PS3 24V 2.0 (50) 1.2 (28) A B With major offices worldwide. World Headquarters, Allen-Bradley, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444 Publication 1794-5.71 May 2000 PN955134 30 Copyright 2000 Allen-Bradley Company, Inc. Printed in USA