ANTOINE LAPORTE VILLE DE REPENTIGNY VERS UNE GESTION DURABLE ET RESPONSABLE DES RESSOURCES EN EAU CARA LE 19 OCTOBRE 2012
LES AMÉLIORATIONS APPORTÉES À LA COLLECTE DES EAUX BRUTES
LA PROBLÉMATIQUE D APPROVISIONNEMENT EN EAU BRUTE STATION DE POMPAGE D EAU BRUTE SITUÉE EN ZONE INONDABLE POMPES ET DÉGRILLEUR SITUÉS SOUS LE NIVEAU ANNUEL DES HAUTES EAUX ENLISEMENT PÉRIODIQUE DU DÉGRILLEUR DANS PLUS D UN MÈTRE DE SABLE ENSABLEMENT RÉCURRENT DES COMPARTIMENTS DE POMPAGE ENSABLEMENT DU PRÉTRAITEMENT ET DES DÉCANTEURS VIDANGES RÉPÉTÉES DES INSTALLATIONS ENSABLÉES RECONDITIONNEMENT RÉPÉTÉ DES POMPES BASSE PRESSION BLOCAGE DES VANNES MURALES ET PAPILLONS TRAVAIL EN ESPACE CLOS LONG ET FASTIDIEUX PERTURBATION DES OPÉRATIONS DURANT LES POINTES DE DÉBIT BLOCAGE DE LA PRISE D EAU PAR DU FRASIL EN DÉCEMBRE
LA RIVIÈRE L ASSOMPTION ET SES TRIBUTAIRES JOLIETTE PARC DU MONT-TREMBLANT L ASSOMPTION REPENTIGNY
L APPROVISONNEMENT D URGENCE SUITE À L ENLISEMENT DE LA STATION DE POMPAGE D EAU BRUTE LE 26 AVRIL 2008 STATION DE POMPAGE POMPE ET GÉNÉRATRICE PUITS DE POMPAGE D URGENCE
ENSABLEMENT DES COMPARTIMENTS DE POMPAGE
LA CONCEPTION DE LA NOUVELLE STATION DE POMPAGE D EAU BRUTE RECHERCHE SUR LES NORMES APPLICABLES LES PLUS RÉCENTES CONSULTATION TECHNIQUE AUPRÈS DU PERSONNEL D EXPLOITATION SPÉCIFICATION DES NORMES DANS LES CLAUSES GÉNÉRALES DES DEVIS SPÉCIFICATION DES ÉQUIPEMENTS AVEC MÉCANISMES DE PROTECTION INTÉGRÉS INTÉGRATION DES ÉQUIPEMENTS DANS LES PLANS POUR FIN DE SOUMISSION RENCONTRE DE COORDINATION ENTRE LES DIFFÉRENTES DISCIPLINES SUIVI DE L ÉVOLUTION DES PLANS ET DEVIS PAR LE PERSONNEL D OPÉRATION SENSIBILITÉ DE L ADMINISTRATION ET DES ÉLUS POUR UN PROJET STRUCTURANT APPROBATION DES PLANS ET DEVIS PAR LE MDDEP & APPEL D OFFRE PUBLIQUE CONSTRUCTION & MISE EN OPÉRATION DE LA NOUVELLE STATION DE POMPAGE
LA NOUVELLE STATION DE POMPAGE D EAU BRUTE
LE DÉGRILLAGE ET LE DESSABLAGE DE L EAU BRUTE DÉGRILLEUR HAUTES EAUX VANNES CONDUITE D EAU BRUTE BASSES EAUX OUVERTURE VERS LE PUITS DE POMPAGE PUITS DE DESSABLAGE ÉCOULEMENT POMPE À SOLIDES
LE DÉGRILLAGE ET LE DESSABLAGE DE L EAU BRUTE DÉGRILLEUR VANNE ACCÈS PUITS POMPE À SABLE
LE PUITS DE POMPAGE D EAU BRUTE DÉGRILLEUR POMPE D EAU BRUTE ESCALIER FONDS EN PENTE VERS LES PUITS DE DESSABLAGE
L ÉCLAIRAGE DES PUITS DE DESSABLAGE ET DE POMPAGE PROJECTEURS INTÉGRÉS DANS LE PLANCHER
LA VENTILATION DES PUITS DE DESSABLAGE ET DE POMPAGE PONT-ROULANT
DES ÉQUIPEMENTS À LA FINE POINTE DE LA TECHNOLOGIE POMPES DÉGRILLEUR VANNES
OBJECTIFS ATTEINTS ENLÈVEMENT COMPLET DU SABLE PAR LES TROIS ÉTAPES DE DESSABLAGE NETTOYAGE DES PUITS DE POMPAGE ET DE DESSABLAGE EN QUELQUES HEURES GAIN ÉNORME DE PRODUCTIVITÉ AVEC UNE VIDANGE QUI NE DEVIENT QUE PONCTUELLE INTÉGRATION RÉUSSIE DES NORMES CSA Z460-05 & Z462-08 AU DESIGN DE L INSTALLATION MANIPULATION AISÉE DES ÉQUIPEMENTS DE PROCÉDÉ PAR LE PONT ROULANT PAS DE BLOCAGE DE LA PRISE D EAU PAR DU FRASIL L HIVER DERNIER STATION DE POMPAGE D EAU BRUTE SANS ENTRÉE EN ESPACE CLOS : - ACCÈS SÉCURITAIRES AUX PUITS DE POMPAGE ET DE DESSABLAGE - VENTILATION PERMANENTE DES POSTES DE TRAVAIL - ÉCLAIRAGE FIXE PAR LE BIAIS DE PROJECTEURS ACCESSIBLES
FAIRE FACE À UN APPROVISIONNEMENT EN EAU BRUTE DÉFICIENT SUBMERGENCE INSUFFISANTE DE LA PRISE D EAU VUE DU BARRAGE DE RETENUE
BRÈCHE IMPORTANTE DANS LA SECTION NORD DU BARRAGE BRÈCHE SECTION NORD
COLMATAGE DE LA BRÈCHE DANS LA SECTION NORD DU BARRAGE RAMPE D ACCÈS VUE DU PONT
LES AMÉLIORATIONS APPORTÉES À LA FILIÈRE DE TRAITEMENT
LA VARIABILITÉ DE LA QUALITÉ DE L EAU BRUTE PARAMÈTRE MINIMUM MOYENNE MAXIMUM TURBIDITÉ UTN 3 30 377 COULEUR UCV 23 71 366 ALCALINITÉ mg/l CaCO 3 13 36 79 DURETÉ mg/l CaCO 3 19 45 88 FER mg/l 0,092 0,276 0,819 MANGANÈSE mg/l 0,004 0,067 0,390 AZOTE AMMONIACAL mg/l 0,09 0,27 0,70 COT mg/l 3,10 4,95 7,39 COLIFORMES FÉCAUX /100 ml 100 753 6 500 SPORES AÉROBIES /100 ml 750 5 690 36 000
1992 - PROCÉDÉ UNITAIRE DE TRAITEMENT MÉLANGE & CONTACT DOSAGE RÉACTIF ORDINATEUR ANALYSEURS ÉCHANTILLON LABORATOIRE
2010 - TRAITEMENT CONVENTIONNEL PERFORMANT SULFATE FERRIQUE ou PASS POLYMÈRE CHARBON ACTIF CHAUX PASS EAU DE JAVEL OZONE ALIMENTATION PRÉTRAITEMENT DÉCANTATION FILTRATION OZONATION ph ALCALINITÉ (CONDUCTIVITÉ) TURBIDITÉ ALCALINITÉ (CONDUCTIVITÉ) SCD ph ph TURBIDITÉ TURBIDITÉ ph COMPTE DE PARTICULES TURBIDITÉ OZONE RÉSIDUEL SOUDE ph EAU DE JAVEL SILICATE POST-TRAITEMENT TURBIDITÉ CHLORE LIBRE ET TOTAL DISTRIBUTION ALCALINITÉ (CONDUCTIVITÉ) ph TURBIDITÉ CHLORE LIBRE
2012 NOUVELLES EXIGENCES DU RÈGLEMENT SUR LA QUALITÉ DE L EAU POTABLE (RQEP) RESSERREMENT DE L ABATTEMENT DES PATHOGÈNES RÉGLEMENTÉS 99,99% DE OOCYSTES DE CRYPTOSPORIDIUM (> 4 LOG) 99,999% DE KYSTES DE GIARDIA (> 5 LOG) 99,9999% DE VIRUS (> 6 LOG) RESSERREMENT DE LA GÉNÉRATION DE SOUS-PRODUITS DÉSINFECTION TRIHALOMÉTHANES TOTAUX à 80 μg/l BROMATES à 10 μg/l ACIDES HALOACÉTIQUES à 60 μg/l
PERFORMANCE D UN PROCÉDÉ CONVENTIONNEL DE TRAITEMENT ABATTEMENT DES PATHOGÈNES = CRÉDITS D ENLÈVEMENTS PHYSIQUES + PERFORMANCES DES ÉTAPES DÉSINFECTIONS
LIMITATIONS RÉGLEMENTAIRES DES PERFORMANCES D UN PROCÉDÉ CONVENTIONNEL SUR L ABATTEMENT DE CRYPTOSPORIDIUM CRÉDITS D ENLÈVEMENT À L EAU FILTRÉE POUR LA TURBIDITÉ : UNE TURBIDITÉ INFÉRIEURE À 0,15 UTN DONNE DROIT À 3,0 LOG D ABATTEMENT D OOCYSTES DE CRYPTOSPORIDIUM INEFFICACITÉ DES ÉTAPES DE DÉSINFECTION EN EAU FROIDE : LES TRAITEMENTS PAR CHLORATION ET OZONATION, ESTIMÉS PAR LE CALCUL DES CT, N ONT QU UN EFFET NÉGLIGEABLE SUR L ABATTEMENT DES OOCYSTES DE CRYPTOSPORIDIUM
RÉACTEUR TROJAN SWIFT 6L24 À MOYENNE PRESSION
BATTERIE DE 4 RÉACTEURS UV AVEC REDONDANCE
POSTE DE RELÈVEMENT DE 4 POMPES MYERS DE 50HP
AGRANDISSEMENT DE LA STATION DE PURIFICATION
2012 - PROCÉDÉ À BARRIÈRES MULTIPLES POUR L ABATTEMENT DES PATHOGÈNES ABATTEMENT DES PATHOGÈNES = CRÉDITS D ENLÈVEMENTS PHYSIQUES + PERFORMANCES DES ÉTAPES DÉSINFECTIONS + BARRIÈRE D INACTIVATION AUX RAYONNEMENTS UV