Light Management Hub. Installation Guide. Please Read. Contents



Documents pareils
Panneau d alimentation de Store Cellulaire

Paxton. ins Net2 desktop reader USB

Quick start guide. HTL1170B

Contrôle d'accès Access control. Notice technique / Technical Manual

03/2013. Mod: WOKI-60IP/TR. Production code: DTWIC 6000

Notice Technique / Technical Manual

Instructions Mozilla Thunderbird Page 1

SERVEUR DÉDIÉ DOCUMENTATION

Le No.1 de l économie d énergie pour patinoires.

Thank you for choosing the Mobile Broadband USB Stick. With your USB Stick, you can access a wireless network at high speed.

Folio Case User s Guide

Package Contents. System Requirements. Before You Begin

GIGABIT PCI DESKTOP ADAPTER DGE-530T. Quick Installation Guide+ Guide d installation+

Logitech Tablet Keyboard for Windows 8, Windows RT and Android 3.0+ Setup Guide Guide d installation

How to Login to Career Page

Lavatory Faucet. Instruction Manual. Questions?

Thank you for choosing the Mobile Broadband USB Stick. With your USB Stick, you can access a wireless network at high speed.

Quick Installation Guide TEW-AO12O

INVESTMENT REGULATIONS R In force October 1, RÈGLEMENT SUR LES INVESTISSEMENTS R En vigueur le 1 er octobre 2001

SA-32 / SA-62 INSTRUCTION MANUAL - MANUEL D INSTRUCTIONS

Logitech Speaker System Z553 Setup Guide Guide d installation

Règlement sur le télémarketing et les centres d'appel. Call Centres Telemarketing Sales Regulation

PAR RINOX INC BY RINOX INC PROGRAMME D INSTALLATEUR INSTALLER PROGRAM

Warning: Failure to follow these warnings could result in property damage, or personal injury.

Fabricant. 2 terminals

Credit Note and Debit Note Information (GST/ HST) Regulations

ASSEMBLY INSTRUCTIONS DIRECTIVES POUR L'ASSEMBLAGE ombre pendant lamp lampe suspendue à tons dégradés, chocolat

Software and Hardware Datasheet / Fiche technique du logiciel et du matériel

ASSEMBLY INSTRUCTIONS DIRECTIVES POUR L'ASSEMBLAGE luster chandelier lamp chandelier à trois branches en verre lustré

Quick Start Guide This guide is intended to get you started with Rational ClearCase or Rational ClearCase MultiSite.

Contrôle électronique pour chambres froides

TABLE DES MATIERES A OBJET PROCEDURE DE CONNEXION

Contents Windows

Guide d'installation rapide TFM-560X YO.13

INSTRUMENTS DE MESURE SOFTWARE. Management software for remote and/or local monitoring networks

Cheque Holding Policy Disclosure (Banks) Regulations. Règlement sur la communication de la politique de retenue de chèques (banques) CONSOLIDATION

DOCUMENTATION - FRANCAIS... 2

Support Orders and Support Provisions (Banks and Authorized Foreign Banks) Regulations

Now enhanced with powerful workplace solutions Maintenant amélioré, diet+ vous offre de puissantes solutions novatrices pour le milieu de travail

Guide d installation Deco Drain inc. DD200

Fonctions intégrées. Nouvelles solutions universelles & système de communication

Garage Door Monitor Model 829LM

WEB page builder and server for SCADA applications usable from a WEB navigator

First Nations Assessment Inspection Regulations. Règlement sur l inspection aux fins d évaluation foncière des premières nations CONSOLIDATION

F1 Security Requirement Check List (SRCL)

DOCUMENTATION - FRANCAIS... 2

LG Electronics, Inc. Display Limited Warranty - USA

Quick Installation Guide TW100-BRV304

Règlement sur les baux visés à la Loi no 1 de 1977 portant affectation de crédits. Appropriation Act No. 1, 1977, Leasing Regulations CODIFICATION

3615 SELFIE. HOW-TO / GUIDE D'UTILISATION

PRESENTATION REMOTE TÉLÉCOMMANDE DE PRÉSENTATION. User Guide Manuel de l utilisateur

PIB : Définition : mesure de l activité économique réalisée à l échelle d une nation sur une période donnée.

Le Cloud Computing est-il l ennemi de la Sécurité?

Export Permit (Steel Monitoring) Regulations. Règlement sur les licences d exportation (surveillance de l acier) CONSOLIDATION CODIFICATION

APPENDIX 6 BONUS RING FORMAT

Compléter le formulaire «Demande de participation» et l envoyer aux bureaux de SGC* à l adresse suivante :

Contrôle d accès Access control MOD-TCPIP-AI. Notice technique / Technical Manual

INDIVIDUALS AND LEGAL ENTITIES: If the dividends have not been paid yet, you may be eligible for the simplified procedure.

General Import Permit No. 13 Beef and Veal for Personal Use. Licence générale d importation n O 13 bœuf et veau pour usage personnel CONSOLIDATION

Quick Installation Guide TV-IP400 TV-IP400W

Loi sur l aide financière à la Banque Commerciale du Canada. Canadian Commercial Bank Financial Assistance Act CODIFICATION CONSOLIDATION

Application Form/ Formulaire de demande

DOCUMENTATION MODULE BLOCKCATEGORIESCUSTOM Module crée par Prestacrea - Version : 2.0

Règlement relatif à l examen fait conformément à la Déclaration canadienne des droits. Canadian Bill of Rights Examination Regulations CODIFICATION

WINTER BOAT STORAGE SYSTEM SYSTÈME DE REMISAGE HIVERNAL POUR BATEAU

Nouveautés printemps 2013

Appointment or Deployment of Alternates Regulations. Règlement sur la nomination ou la mutation de remplaçants CONSOLIDATION CODIFICATION

Gestion des prestations Volontaire

RULE 5 - SERVICE OF DOCUMENTS RÈGLE 5 SIGNIFICATION DE DOCUMENTS. Rule 5 / Règle 5

Railway Operating Certificate Regulations. Règlement sur les certificats d exploitation de chemin de fer CODIFICATION CONSOLIDATION

worldwide limited warranty and technical support

Interest Rate for Customs Purposes Regulations. Règlement sur le taux d intérêt aux fins des douanes CONSOLIDATION CODIFICATION

Comfort Duett. TV-kit. USA: English/Français/Español. Comfort Duett

Avis certifiant que des pays accordent les avantages du droit d auteur. Certification of Countries Granting Equal Copyright Protection Notice

that the child(ren) was/were in need of protection under Part III of the Child and Family Services Act, and the court made an order on

Tutoriel de formation SurveyMonkey

Name Use (Affiliates of Banks or Bank Holding Companies) Regulations

Calculation of Interest Regulations. Règlement sur le calcul des intérêts CONSOLIDATION CODIFICATION. Current to August 4, 2015 À jour au 4 août 2015

AUTO ER ADAPT ER SPECIAL USE WARNING

Once the installation is complete, you can delete the temporary Zip files..

Monitor LRD. Table des matières

Instructions pour mettre à jour un HFFv2 v1.x.yy v2.0.00

Quick Installation Guide TBW-106UB H/W: V1

If the corporation is or intends to become a registered charity as defined in the Income Tax Act, a copy of these documents must be sent to:

Practice Direction. Class Proceedings

Manuel de l utilisateur

PARIS ROISSY CHARLES DE GAULLE

Stainless Steel Solar Wall Light

Resident Canadian (Insurance Companies) Regulations. Règlement sur les résidents canadiens (sociétés d assurances) CONSOLIDATION CODIFICATION

Nordion Europe S.A. Incorporation Authorization Order. Décret autorisant la constitution de Nordion Europe S.A. CONSOLIDATION CODIFICATION

AND / ET USER GUIDE UK HARDWIRED CONTROL PANEL UK GUIDE UTILISATEUR CENTRALE D ALARME FILAIRE F

Trim Kit Installation Instruction

Utiliser une WebCam. Micro-ordinateurs, informations, idées, trucs et astuces

The new consumables catalogue from Medisoft is now updated. Please discover this full overview of all our consumables available to you.

Critères à l attention des fabricants et des fournisseurs de biens ou de services : dispositifs mécaniques pour bingo

Form of Deeds Relating to Certain Successions of Cree and Naskapi Beneficiaries Regulations

accidents and repairs:

Subject to the terms of this Agreement, Adobe hereby grants you a nonexclusive,

22/09/2014 sur la base de 55,03 euros par action

APPENDIX 2. Provisions to be included in the contract between the Provider and the. Holder

Transcription:

Light Management Hub Installation Guide Please ead Contents System Overview 2 Hub Overview 3 Model Number Guide 4 Dimensions 5 Mounting and Conduit Entry 6 Line Voltage Wiring 7 Bus Supply Wiring 8 Link: Bus Supply System Diagram 9 Bus Supply OPT Switches and LEDs 10 Ethernet Wiring 11 Configurable Link Wiring: Power Panel Link 12 Configurable Link Wiring: GAFIK Eye QS and Sivoia QS Shades 13 Activate the System 14 Warranty 15 Contact Information 16 The light management hub provides the ability to control Lutron digital ballast modules, Lutron GAFIK Eye power panels, GAFIK Eye QS, and Sivoia QS shades from one centralized location.

lutron lutron LUTON LUTON LUTON LUTON lutron lutron LUTON LUTON LUTON LUTO N LUTO N lutron lutron LUTON LUTON LUTON LUTON lutron TM System Overview 120 V normal/emergency feed To BMS by others (BACnet IP) Dedicated Green Glance client PC and display (optional) Corporate Internet firewall (by others) Hub To additional floors Power Panel Link Q-Admin control and monitor on client PC (optional) Corporate Intranet Network Q-Manager server Lutron interprocessor communication link Loops GP/LP Dimming Panel QS Shade Link To dimming panel loads To switching panel loads XP Switching Panel QS Control Link seetouch QS master wallstations seetouch QS master wallstation wallstation Occupant sensor Interior Office Closed office ballasts and sensors I sensor GAFIK Eye QS with S232 interface Incandescent loads LV loads ballast To touchscreen by others Occupant sensor Interior Conference oom Open office ballasts and sensors QS smart power panel QS shade control Daylight sensor QS smart power panel I sensor GAFIK Eye QS with QS smart power panel ballast QS shades QS shades Occupant and daylight sensors QS shades Open Office Areas Exterior Office Exterior Conference oom 2 TM Light Management Hub

Hub Overview Line voltage input, normal/ emergency feed eceptacle (for Lutron service use only) Hub power switch PELV (Class 2: USA) power supply board Power supply LEDs PELV (Class 2: USA) configurable link wire trough Digital ballast loop wire trough TM bus supplies (4 modules, 2 loops per module maximum) Bus supply LEDs Factory configured link Configurable links (power panel, Sivoia QS shades, or bus supply) Processor LEDs 5-port unmanaged Ethernet device processors (2 maximum) TM Light Management Hub 3

Model Number Guide Example QP2-2P8CSE - 120 Prefix Voltage Number of Processors Number of Loops Switch Type Available Model Numbers Contact Lutron for options not listed below. QP2-0P0CSE-120 QP2-1P0CSE-120 QP2-1P2CSE-120 QP2-1P4CSE-120 QP2-1P6CSE-120 QP2-1P8CSE-120 QP2-2P0CSE-120 QP2-2P2CSE-120 QP2-2P4CSE-120 QP2-2P6CSE-120 QP2-2P8CSE-120 Prefix QP2 = TM Processor Number of Processors 0P = 0 processors 1P = 1 processor 2P = 2 processors Number of Loops 0C = 0 loops 2C = 2 loops 4C = 4 loops 6C = 6 loops 8C = 8 loops Switch Type SE = Ethernet 5-port Voltage 120 for 120 V Additional atings 50 / 60 Hz Output: - 18 V 250 ma per loop Processor - 24 V 1 A per link QS Device Consumption ules The table below lists the devices available on the QS link. See below for each device s count toward the link maximums for switch legs, devices, and power draw. A QS link can have up to 512 switch legs (outputs), 99 devices, and 32 power draw units. QS Device Description Switch Leg Count Device Count Power Draw Units 3-zone GAFIK Eye QS 3 1 0 4-zone GAFIK Eye QS 4 1 0 6-zone GAFIK Eye QS 6 1 0 seetouch QS 0 1 1 Sivoia QS oller 64TM 1 1 0 Sivoia QS oller 100TM 1 1 0 Sivoia QS oller 225TM 1 1 0 6-zone GAFIK Eye QS with up to 64 1 0 8-zone GAFIK Eye QS with up to 64 1 0 16-zone GAFIK Eye QS with up to 64 1 0 QS contact closure interface up to 5 1 2 QS network interface 0 1 2 QS smart power panel 0 1 0 4 TM Light Management Hub

Dimensions All dimensions in inches (mm) 15.75 (400) Top View 2.5 (63.5) 15.75 (400) 12.75 (324) 5.81 (148) 0.15 (4) 31.5 (800) 26.5 (673) 31.5 (800) Left Side View Front View ight Side View Bottom View TM Light Management Hub 5

Mounting and Conduit Entry Ceiling Dedicated feed Line voltage only Digital ballast loops NEC Class 1 or PELV (Class 2: USA) only PELV (Class 2: USA) wiring only for control links and Ethernet connection Alternate ballast wiring entry Alternate ballast wiring entry Alternate PELV (Class 2: USA) entry Alternate PELV (Class 2: USA) entry Wall Alternate ballast wiring entry Alternate PELV (Class 2: USA) entry Front View Side View Notes Water damages equipment. Mount in a location where the hub and processors will not get wet. Mount within 7 of true vertical. Digital ballast wiring can be Class 1 or Class 2; always keep Class 1 and Class 2 wiring separate, and follow all applicable local and national electric codes. A minimum of 12 in (305 mm) unobstructed space is required in front of and below the hub for ventilation. Enclosure: NEMA Type 1, IP-20 protection #16 U.S. gauge steel Weight: 45 pounds (20.4 kg) Surface mount only For indoor use only 32-104 ºF (0-40 ºC) elative humidity less than 90% non-condensing 6 TM Light Management Hub

GND N 120 V N/E Line Voltage Wiring eceptacle for Lutron use only Ground/Earth (green) Neutral (white) Hot/Live (black) Notes Line voltage must enter hub from top right of hub un a dedicated 120 V normal/emergency feed un wiring so line (mains) Class 1 voltage is separate from PELV (Class 2: USA) wiring Wire Sizes Power feed (hot/live): 14-10 AWG (2.5-4.0 mm 2 ) TM Light Management Hub 7

TM Bus Supply Wiring Line voltage in (prewired by Lutron) 1 2 3 4 5 6 7 8 DL7 DL8 EM C Processor link (prewired by Lutron; not visible in this view) Emergency input (normally closed) devices Wire Gauge Max. Bus Length 12 AWG 2200 ft (670 m) 14 AWG (2.5 mm 2 ) 1400 ft (427 m) 16 AWG (1.5 mm 2 ) (1.5 mm 2 ) 900 ft (274 m) 18 AWG (1.0 mm 2 ) (1.0 mm 2 ) 570 ft (175 m) To additional devices Notes and wires are not polarity sensitive. Hot/live, neutral, and ground wires are also connected to each lighting fixture; some may have an emergency feed. bus uses a free wire topology. If 15 V +/- 1 V is not present between and, check the bus supply wiring. A short between and will cause the bus supply to stop providing voltage on the bus and will cause the E indicator to flash. emoving the short between and will allow the bus supply to operate properly. To wire the bus supply for PELV (Class 2: USA), the bus supply wires must be separated from the mains wiring. Otherwise, the PELV wiring must be classified as NEC Class 1. 8 TM Light Management Hub

Link: TM Bus Supply System Diagram Notes bus may be wired in accordance with NEC Class 1 or PELV (Class 2: USA) practices Sensors and bus supply contact closures must be wired PELV (Class 2: USA) Dedicated link; prewired by Lutron to Bus Supply located in hub Note: If link is not required, this can be used as a configurable link. QP2-2P8CSE-120 shown Bus Supply System Diagram To additional ballasts and modules (up to 64 total) ballast 1 2 3 4 5 6 7 8 module Eco10 or HiLume ballast* ballast ballast I receiver Lighting remote bus supply (in hub) Occupant sensor (32 max. per loop) Keypad * Does not count as one of the ballasts or modules on the bus Daylight sensor (8 max. per loop) TM Light Management Hub 9

TM Bus Supply OPT Switches and LEDs H/L H/L N N ON1 2 3 4 5 6 7 8 6 7 8 OFF ON position position OPT Switches OPT switches are used to configure the Bus Supply. The tables below describe the options. To place an OPT switch in the OFF position, slide the switch to the left; away from the switch s number. Default is ON (next to the switch s number). OPT Switch Functions 1 Addressing Set address for 2 bus supply s loops 3 (2 loops per bus supply) 4 Green loop (right side) Manual override levels 5 6 Blue loop (left side) Manual Override levels 7 8 Manual Override ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 ON 5 7 1 3 6 8 2 4 7 3 5 8 4 6 5 7 6 8 7 8 Bus Supply 1 Addresses 1, 2 ON 1 2 3 4 5 6 7 8 Lights stay at current level Lights stay at current level ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 5 7 3 6 8 4 7 5 8 6 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 7 5 3 8 6 4 7 5 8 6 7 8 Manual override levels will be used ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 5 7 3 6 8 4 7 5 8 6 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 7 5 3 8 6 4 7 5 8 6 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 7 5 3 8 6 4 7 5 8 6 7 8 Bus Supply 2 Addresses 3, 4 Lights go to high level Lights go to high level ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 5 7 3 6 8 4 7 5 8 6 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 7 5 3 8 6 4 7 5 8 6 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 ON 7 5 1 3 8 6 2 4 7 3 5 8 4 6 5 7 6 8 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 7 5 3 8 6 4 7 5 8 6 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 7 5 3 8 6 4 7 5 8 6 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 ON 7 5 1 3 8 6 2 4 7 3 5 8 4 6 5 7 6 8 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 7 5 3 8 6 4 7 5 8 6 7 8 Bus Supply 3 Addresses 5, 6 Lights go to low level Lights go to low level ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 ON 7 5 1 3 8 6 2 4 7 3 5 8 4 6 7 5 8 6 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 7 5 3 8 6 4 7 5 8 6 7 8 ON 1 2 3 4 5 6 7 8 ON 1 2 ON 1 3 2 4 ON 3 5 1 4 6 2 7 5 3 8 6 4 7 5 8 6 7 8 Bus Supply 4 Addresses 7, 8 Lights will go to the level specified by the system Lights go to Off Lights go to Off H/L H/L N N 5 6 7 8 Status LEDs LEDs on the Bus Supply indicate network status. The specific LEDs, color and flashing method is detailed below. blue loop E E STAT V ON 1 2 3 4 5 6 7 8 PW green loop E E STAT V PW LED Normal Operation Problem Indicator Probable Cause V PW On Off No Mains power STAT Steady flash Off No Mains power or unit fault E / Intermittent flash or Off On On Unit fault Unit fault Off On Emergency contact closure is active Steady flash Miswire detected on corresponding bus 10 TM Light Management Hub

TM Ethernet Wiring Example of Ethernet Wiring: iser Diagram Light Management Hub Floor Light Management Hub Floor Ethernet device Light Management Hub Light Management Hub To additional Light Management Hubs Notes Ethernet wiring is considered PELV (Class 2: USA); do not run in the same conduit as line (mains) voltage wiring. Wiring distance for any single Ethernet data link segment is 330 ft (100 m) max; use switches or hubs for longer distances. Processors cannot be more than 6 devices away from the server. Processors communicate over the Ethernet network using TCP/IP and multicast UDP; a dedicated network must be used for the lighting control system. Light Management Hub Floor server Unmanaged switch TM Light Management Hub 11

Configurable Link Wiring: Power Panel Link Processor link terminal Power panel Power panel Power panel DAIN V+ COM 5 4 3 2 1 1 COM 2 N/C 3 4 D DAIN 5 Sense line 1 COM 2 N/C 3 4 D DAIN 5 Sense line 1 COM 2 N/C 3 4 D DAIN 5 Sense line Link terminator (LT-1) 4 3 3 4 Control wiring (1) 12 AWG (2.5 mm 2 ) 1: Common Data link (1) shielded, twisted pair 22 AWG (1.0 mm 2 ) 3: 4: D: Drain wire in shield (keep away from ground and all electronics PELV Terminal Wiring Link terminator (LT-1) Emergency/essential sense line (1) 18 AWG (1.0 mm 2 ) 5: Sense line Sense line is used when there is a panel being supplied by an emergency/essential feed Configurable links (2) 12 AWG (2.5 mm 2 ) Drain Data link: twisted, shielded pair 22 AWG (1.0 mm 2 ) 3: 4: Sense: 18 AWG (1.0 mm 2 ) 1 2 3 4 D 5 C D Notes Power panel link must be daisy-chained (no T-taps). Maximum of 32 power panels per link. It is not necessary to have the hub at the end of the link. The sense wire (terminal 5) is used whenever there is a panel being supplied by an emergency/essential feed; see power panel instructions for details. Each low-voltage PELV (Class 2: USA) terminal can accept only two 18 AWG (1.0 mm 2 ) wires. Two 12 AWG (2.5 mm 2 ) conductors will not fit. Connect as shown using appropriate wire connectors. Common 24VFW Data A OK Drain Sense Link A B Power OK Link Comm Data B OK 1 2 3 4 D 5 C D SELECT CICUIT Drain Total length of control link may be no more than 2000 ft. (600 m). If link repeater interface and GX-CBL-46L cable are used, length may be up to 4000 ft. (1200 m). GX-CBL-46L PELV (Class 2: USA) wiring cable is available from Lutron and contains two 12 AWG (2.5 mm 2 ) conductors for control power, one twisted, shielded pair of 22 AWG (1.0 mm 2 ) for data link, and one 18 AWG (1.0 mm 2 ) conductor for emergency (essential) sense line. 12 TM Light Management Hub

Configurable Link Wiring: GAFIK Eye QS and Sivoia QS Shades DAIN V+ COM 5 4 3 2 1 GAFIK Eye QS Link (do not use the DAIN terminal) GAFIK Eye QS control unit QS wallstations 4 3 2 1 4 3 2 1 4 3 2 1 Configurable links Note: Wallstations are powered directly from the light management hub (not the GAFIK Eye QS control unit) PELV Terminal Wiring (2) 12 AWG (2.5 mm 2 ) Drain Data link: (1) twisted, shielded pair 22 AWG (1.0 mm 2 ) 3: 4: 4 3 2 1 Sivoia QS Shade Link (do not use the DAIN terminal) (2) 12 AWG (2.5 mm 2 ) C B A DAIN V+ COM 5 4 3 2 1 1 2 A B C GAFIK Eye QS control unit PELV (Class 2: USA) control wiring (2) 18 AWG (1.0 mm 2 ) 1: Common 2: 24 V 1 2 3 4 1 2 3 4 5 6 L N Sivoia QS shade Sivoia QS smart power supply panel Wire Gauge QS Link Max. Length 12 AWG (2.5 mm 2 ) 2000 ft (600 m) 16 AWG (1.5 mm 2 ) 800 ft (250 m) 18 AWG (1.0 mm 2 ) 500 ft (150 m) Notes System communication uses PELV (Class 2: USA) low-voltage wiring. Follow all local and national electrical codes when installing PELV (Class 2: USA) wiring with line voltage/mains wiring. Each terminal accepts up to two 18 AWG (1.0 mm 2 ) wires. Total length of control link must not exceed 2000 ft (600 m); If exceeding 2000 ft (600 m), contact Lutron for wiring configuration. Make all connections in the control unit s wallbox. A QS link can have up to 512 switch legs (outputs), 99 devices, and 32 power draw units (see page 4). Wiring can be T-tapped or daisy-chained. Wire sizes: - Two 12 AWG (2.5 mm 2 ) conductors for control power. - One twisted, shielded pair of 22 AWG (1.0 mm 2 ) for data link. - Cable is available from Lutron: GX-CBL-46L. TM Light Management Hub 13

Activate the System You have completed your system installation. For onsite factory startup, call Lutron Technical Support and select Startup to schedule a field service visit. Allow for 10 working days between day of call and scheduled visit. In the U.S., Canada, and the Caribbean: 1.800.523.9466 In Mexico: 888.235.2910 In Europe: +44.207.702.0657 In Asia: +65.6220.4666 In Japan: +81.355.758.411 In all other countries: +1.610.282.6701 H/L H/L N L2 N L1 E E STAT V ON 1 2 3 4 5 6 7 8 PW LNK PW OK LNK PW OK LNK PW OK E E STAT V 5 6 7 8 PW L2 Tx x L2 Heartbeat L1 Tx x L1 Heartbeat Processor Tx x Processor Heartbeat Error Power LED Power Supply LNK PW OK Bus Supply E / STAT Normal Operation Problem Indicator Probable Cause and Solution On Off No power from transformer: Check that power feed and power switch are on Off On Emergency contact closure is active Flash* or Off Steady flash Steady flash* On Off On Miswire detected on corresponding bus: Check wiring Unit fault or debug mode: Check to see if bus supply is in debug mode No power or unit fault Unit fault V PW On Off No power Processor L1/L2 Tx x No links L1/L2 Heartbeat No links L1/L2 Tx x with link L1/L2 Heartbeat with link Processor Tx x Processor Heartbeat Off Off Link error: un software diagnostics Flashing Off Link error: un software diagnostics Flashing Off Link error: un software diagnostics Flashing Off Link error: un software diagnostics Off On Software uploading Flashing Boot mode Flashing Flashing Boot mode (if Tx x also flashing) Error Off On Link error: un software diagnostics Power On Off Check power supply * If the bus supply E/ and LEDs are both flashing in unison, the bus supply is in boot mode. 14 TM Light Management Hub

Warranty Lutron Electronics Co., Inc. One Year Limited Warranty For a period of one year from the date of purchase, and subject to the exclusions and restrictions described below, Lutron warrants each new unit to be free from manufacturing defects. Lutron will, at its option, either repair the defective unit or issue a credit equal to the purchase price of the defective unit to the Customer against the purchase price of comparable replacement part purchased from Lutron. eplacements for the unit provided by Lutron or, at its sole discretion, an approved vendor may be new, used, repaired, reconditioned, and/or made by a different manufacturer. If the unit is commissioned by Lutron or a Lutron approved third party as part of a Lutron commissioned lighting control system, the term of this warranty will be extended, and any credits against the cost of replacement parts will be prorated, in accordance with the warranty issued with the commissioned system, except that the term of the unit s warranty term will be measured from the date of its commissioning. EXCLUSIONS AND ESTICTIONS This Warranty does not cover, and Lutron and its suppliers are not responsible for: 1. Damage, malfunction or inoperability diagnosed by Lutron or a Lutron approved third party as caused by normal wear and tear, abuse, misuse, incorrect installation, neglect, accident, interference or environmental factors, such as (a) use of incorrect line voltages, fuses or circuit breakers; (b) failure to install, maintain and operate the unit pursuant to the operating instructions provided by Lutron and the applicable provisions of the National Electrical Code and of the Safety Standards of Underwriter s Laboratories; (c) use of incompatible devices or accessories; (d) improper or insufficient ventilation; (e) unauthorized repairs or adjustments; (f) vandalism; or (g) an act of God, such as fire, lightning, flooding, tornado, earthquake, hurricane or other problems beyond Lutron s control. 2. On-site labor costs to diagnose issues with, and to remove, repair, replace, adjust, reinstall and/or reprogram the unit or any of its components. 3. Equipment and parts external to the unit, including those sold or supplied by Lutron (which may be covered by a separate warranty). 4. The cost of repairing or replacing other property that is damaged when the unit does not work properly, even if the damage was caused by the unit. EXCEPT AS EXPESSLY POVIDED IN THIS WAANTY, THEE AE NO EXPESS O IMPLIED WAANTIES OF ANY TYPE, INCLUDING ANY IMPLIED WAANTIES OF FITNESS FO A PATICULA PUPOSE O MECHANTABILITY. LUTON DOES NOT WAANT THAT THE UNIT WILL OPEATE WITHOUT INTEUPTION O BE EO FEE. NO LUTON AGENT, EMPLOYEE O EPESENTATIVE HAS ANY AUTHOITY TO BIND LUTON TO ANY AFFIMATION, EPESENTATION O WAANTY CONCENING THE UNIT. UNLESS AN AFFIMATION, EPESENTATION O WAANTY MADE BY AN AGENT, EMPLOYEE O EPESENTATIVE IS SPECIFICALLY INCLUDED HEEIN, O IN STANDAD PINTED MATEIALS POVIDED BY LUTON, IT DOES NOT FOM A PAT OF THE BASIS OF ANY BAGAIN BETWEEN LUTON AND CUSTOME AND WILL NOT IN ANY WAY BE ENFOCEABLE BY CUSTOME. IN NO EVENT WILL LUTON O ANY OTHE PATY BE LIABLE FO EXEMPLAY, CONSEQUENTIAL, INCIDENTAL O SPECIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, DAMAGES FO LOSS OF POFITS, CONFIDENTIAL O OTHE INFOMATION, O PIVACY; INESS INTEUPTION; PESONAL INJUY; FAILUE TO MEET ANY DUTY, INCLUDING OF GOOD FAITH O OF EASONABLE CAE; NEGLIGENCE, O ANY OTHE PECUNIAY O OTHE LOSS WHATSOEVE), NO FO ANY EPAI WOK UNDETAKEN WITHOUT LUTON S WITTEN CONSENT AISING OUT OF O IN ANY WAY ELATED TO THE INSTALLATION, DEINSTALLATION, USE OF O INABILITY TO USE THE UNIT O OTHEWISE UNDE O IN CONNECTION WITH ANY POVISION OF THIS WAANTY, O ANY AGEEMENT INCOPOATING THIS WAANTY, EVEN IN THE EVENT OF THE FAULT, TOT (INCLUDING NEGLIGENCE), STICT LIABILITY, BEACH OF CONTACT O BEACH OF WAANTY OF LUTON O ANY SUPPLIE, AND EVEN IF LUTON O ANY OTHE PATY WAS ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. NOTWITHSTANDING ANY DAMAGES THAT CUSTOME MIGHT INCU FO ANY EASON WHATSOEVE (INCLUDING, WITHOUT LIMITATION, ALL DIECT DAMAGES AND ALL DAMAGES LISTED ABOVE), THE ENTIE LIABILITY OF LUTON AND OF ALL OTHE PATIES UNDE THIS WAANTY On ANY CLAIM FO DAMAGES AISING OUT OF O IN CONNECTION WITH THE MANUFACTUE, SALE, INSTALLATION, DELIVEY, USE, EPAI, O EPLACEMENT OF THE UNIT, O ANY AGEEMENT INCOPOATING THIS WAANTY, AND CUSTOME S SOLE EMEDY FO THE FOEGOING, WILL BE LIMITED TO THE AMOUNT PAID TO LUTON BY CUSTOME FO THE UNIT. THE FOEGOING LIMITATIONS, EXCLUSIONS AND DISCLAIMES WILL APPLY TO THE MAXIMUM EXTENT ALLOWED BY APPLICABLE LAW, EVEN IF ANY EMEDY FAILS ITS ESSENTIAL PUPOSE. TO MAKE A WAANTY CLAIM To make a warranty claim, promptly notify Lutron within the warranty period described above by calling the Lutron Technical Support Center at (800) 523-9466. Lutron, in its sole discretion, will determine what action, if any, is required under this warranty. To better enable Lutron to address a warranty claim, have the unit s serial and model numbers available when making the call. If Lutron, in its sole discretion, determines that an on-site visit or other remedial action is necessary, Lutron may send a Lutron Services Co. representative or coordinate the dispatch of a representative from a Lutron approved vendor to Customer s site, and/or coordinate a warranty service call between Customer and a Lutron approved vendor. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. These products may be covered under the following U.S. patent: 7,391,297; and corresponding foreign patents. Other U.S. and foreign patents may be pending. Lutron, the sunburst logo, Sivoia, Hi-lume, Eco-10,, Tu-Wire, seetouch, and GAFIK Eye are registered trademarks and and the green leaf design are trademarks of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts 2008 Lutron Electronics Co., Inc. TM Light Management Hub 15

Contact Information Internet: www.lutron.com E-mail: product@lutron.com World Headquarters USA Lutron Electronics Co., Inc. 7200 Suter oad Coopersburg, PA 18036-1299 TEL +1.610.282.3800 FAX +1.610.282.1243 Toll-Free 1.888.LUTON1 Technical Support 1.800.523.9466 North and South America Technical Hotlines USA, Canada, Caribbean: 1.800.523.9466 Mexico: +1.888.235.2910 Central/South America: +1.610.282.6701 European Headquarters United Kingdom Lutron EA Ltd. 6 Sovereign Close, London W 3JF United Kingdom TEL +44.(0)20.7702.0657 FAX +44.(0)20.7480.6899 FEEPHONE (UK) 0800.282.107 Technical support +44.(0)20.7680.4481 Asian Headquarters Singapore Lutron GL Ltd. 15 Hoe Chiang oad #07-03 Euro Asia Centre Singapore 089316 TEL +65.6220.4666 FAX +65.6220.4333 Asia Technical Hotlines Northern China: 10.800.712.1536 Southern China: 10.800.120.1536 Hong Kong: 800.901.849 Indonesia: 001.803.011.3994 Japan: +81.3.5575.8411 Macau: 0800.401 Singapore: 800.120.4491 Taiwan: 00.801.137.737 Thailand: 001.800.120.665853 Other countries: +65.6220.4666 Lutron Electronics, Inc. Made and printed in U.S.A. P/N 032-210 ev. A 01/2009

Centre de Contrôle de Gestion d Éclairage Guide d installation Contenu Vue d ensemble du Système 2 Vue d ensemble du Centre de Contrôle 3 Guide du Numéro de Modèle 4 Dimensions 5 Montage et Entrée de Conduit 6 Câblage de Tension de Ligne 7 Câblage de la Barre d Alimentation 8 Lien de l : Schéma de la Barre d Alimentation du Système 9 Barre d Alimentation Interrupteurs OPT et DELs 10 Câblage Ethernet 11 Lien de Câblage Configurable : Lien du Panneau de Puissance 12 Lien de Câblage Configurable : Stores GAFIK Eye QS et Sivoia QS 13 Activer le Système 14 Garantie 15 Information de contact 16 À lire attentivement Le Centre de Contrôle de Gestion d Éclairage procure la capacité de contrôler les modules de ballasts numériques de Lutron, les panneaux de puissance GAFIK Eye de Lutron, le GAFIK Eye QS, et les stores Sivoia QS à partir d un emplacement centralisé.

lutron lutron LUTON LUTON LUTON LUTON lutron lutron LUTON LUTON LUTON LUTO N LUTO N lutron lutron LUTON LUTON LUTON LUTON lutron Vue d ensemble du Système TM Alimentation normale/urgence 120 V BMS par autres (BACnet IP) PC du client avec accès dédié Green GlanceTM et affichage (optionnel) Coupe-feu Internet corporatif (par d autres) Centre de Contrôle Vers planchers additionnels Liaison au Panneau d Alimentation Contrôle Q-Admin et moniteur sur PC du client (optionnel) éseau Intranet Corporatif Serveur Q-Manager Boucles de raccordement Liaison de communication interprocesseur de Lutron Panneau de Gradation GP/LP Liaison Store QS Aux charges de panneaux de gradation Aux charges de panneaux de commutation Panneau de Commutation XP Liaison de Contrôle QS Postes muraux principaux seetouch QS poste mural principal seetouch QS Poste mural Capteur de mouvement de l Occupant Bureau Intérieur Bureau fermé ballasts et détecteurs Détecteur I GAFIK Eye QS avec Interface S232 Charges incandescentes Charges LV Ballast Vers écran tactile par d autres Capteur de mouvement de l Occupant Salle de Conférence Intérieure Bureau ouvert ballasts et détecteurs Panneau d alimentation intelligent QS Contrôle de stores QS Stores QS Capteur de lumière du Détecteur jour I Panneau d alimentation intelligent QS Stores QS Panneau d alimentation intelligent QS GAFIK Eye QS avec Ballast Détecteurs d Occupation et Capteurs de lumière du jour Stores QS Espaces de Bureau à Aire Ouverte Bureau Extérieur Salle de Conférence Extérieure 2 Centre de Contrôle de Gestion d Éclairage TM

Vue générale du Centre de Contrôle Entrée à tension secteur, alimentation normale/urgence Prise (usage service Lutron seulement) Interrupteur d alimentation du Centre de Contrôle PELV (Classe 2 : USA) tableau d alimentation DELs d alimentation PELV (Classe 2 : USA) Caniveau pour câble le lien configurable Caniveau pour boucle de raccordement de ballast numérique Barre d alimentation TM (4 modules, maximum 2 boucles par module) DELs de la Barre d alimentation Configuré en usine Lien Liens configurables (panneau d alimentation, stores Sivoia QS, ou Barre d alimentation ) DELs du Processeur Dispositif Ethernet à 5-ports non utilisés Processeurs (2 maximum) Centre de Contrôle de Gestion d Éclairage TM 3

Guide du Numéro de Modèle Exemple QP2-2P8CSE - 120 Préfixe Nombre de Processeurs Nombre de boucles Tension Type de Commutateur Numéros de Modèles Disponibles Contacter Lutron pour options non affichées ci-dessous. QP2-0P0CSE-120 QP2-1P0CSE-120 QP2-1P2CSE-120 QP2-1P4CSE-120 QP2-1P6CSE-120 QP2-1P8CSE-120 QP2-2P0CSE-120 QP2-2P2CSE-120 QP2-2P4CSE-120 QP2-2P6CSE-120 QP2-2P8CSE-120 Préfixe QP2 = Processeur TM Nombre de Processeurs 0P = 0 Processeur 1P = 1 Processeur 2P = 2 Processeurs Nombre de boucles 0C = 0 boucle de raccordement 2C = 2 boucles de raccordement 4C = 4 boucles de raccordement 6C = 6 boucles de raccordement 8C = 8 boucles de raccordement Type de Commutateur SE = Ethernet 5-ports Tension 120 for 120 V Caractéristiques Nominales Additionnelles 50 / 60 Hz Sortie : - 18 V 250 ma par boucle Processeur - 24 V 1 A par liaison ègles de Consommation du Dispositif QS Le tableau ci-dessous affiche les dispositifs disponibles sur la liaison QS. Voir ci-dessous le décompte maximum des liens, raccordements, dispositifs et unités de puissance pour chacun des dispositifs. Une liaison QS peut avoir jusqu à 512 raccordements (sorties), 99 dispositifs, et 32 unités de puissance. Description du Dispositif QS Décompte de Parcours de Commutateur Décompte de Dispositif Unités de Puissance 3-zones GAFIK Eye QS 3 1 0 4-zones GAFIK Eye QS 4 1 0 6-zones GAFIK Eye QS 6 1 0 seetouch QS 0 1 1 Sivoia QS oller 64TM 1 1 0 Sivoia QS oller 100TM 1 1 0 Sivoia QS oller 225TM 1 1 0 6-zones GAFIK Eye QS avec jusqu à 64 1 0 8-zones GAFIK Eye QS avec jusqu à 64 1 0 16-zones GAFIK Eye QS avec jusqu à 64 1 0 Interface de contact fermé QS jusqu à 5 1 2 Interface de réseau QS 0 1 2 Panneau d alimentation intelligent QS 0 1 0 4 Centre de Contrôle de Gestion d Éclairage TM

Dimensions Toutes les dimensions sont en mm (pouces) 400 (15,75) Vue de dessus 63,5 (2,5) 400 (15,75) 324 (12,75) 148 (5,81) 4 (0,15) 800 (31,5) 673 (26,5) 800 (31,5) Vue du côté gauche Vue de face Vue du côté droit Vue de dessous Centre de Contrôle de Gestion d Éclairage TM 5

Montage et Entrée de Conduit Plafond Alimentation dédiée Tension secteur seulement Boucle de ballast numérique NEC Classe 1 ou PELV (Classe 2 : USA) seulement PELV (Classe 2 : USA) seulement pour câblage de liaison de contrôle et connexion Ethernet Entrée alternative de câblage de ballast Entrée alternative de câblage de ballast Entrée alternative PELV (Classe 2 : USA) Entrée alternative PELV (Classe 2 : USA) Mur Entrée alternative de câblage de ballast Entrée alternative PELV (Classe 2 : USA) Vue de face Vue de profil emarques L eau endommage l équipement. Monter le centre de contrôle et les processeurs dans un endroit à l abri de l eau. Monter à la verticale à l intérieur de 7. Le câblage de ballast numérique peut être Classe 1 ou Classe 2; toujours garder le câblage Classe 1 et Classe 2 séparément, et conformez-vous aux codes électriques local et national applicables. Une espace de minimum 305 mm (12 po) libre d obstruction est requise à l avant et sous le centre de contrôle pour la ventilation. Boîtier : NEMA Type 1, protection IP-20 acier gauge #16 É.U. Poids : 20,4 kg (45 livres) Installation en surface seulement. Pour utilisation intérieure seulement 0-40 ºC (32-104 ºF) Humidité relative moins de 90% sans condensation. 6 Centre de Contrôle de Gestion d Éclairage TM

MALT N 120 V N/E Câblage Tension Secteur Prise pour l utilisation de Lutron seulement MALT (vert) Neutre (blanc) Sous tension (noir) emarques La tension secteur doit entrer par le haut du côté droit du centre de contrôle Faire parcourir un câble d alimentation dédié normal/ urgence à 120 V Faire parcourir le câblage (principal) de façon que la tension Classe 1 soit séparé du câblage PELV (Classe 2 : USA) Dimensions des fils Alimentation (sous tension) : 2,5-4,0 mm 2 (14-10 AWG) Centre de Contrôle de Gestion d Éclairage TM 7